Product FAQs

Ask a Question

What is the minimum load consumption value of an auxiliary ‘OF’ Contact in Masterpact ACB.

There are two types of the OF contact available for Masterpact Air Circuit Breaker (ACB) and the minimum load consumption value of this ON-OFF Indication Contact (OF) is as below-

Standard ‘OF’ Contact
 
Minimum Load      100mA/24V
 
Low Level ‘OF’ Contact
 
Minimum Load      2mA/15V
 
 
Was this helpful?