What is the replacement for EOCR 3DM2 WRDUW,EOCR SS 05 N 220,EOCR SS 30 N 220 and EOCR SS 60 N 220

1. EOCR3DM2WRDUW is a motor protection relay which belongs to the local offer from SE South Korea. This offer is not available globally and also does not have any 1:1 equivalent in the TeSys Range. It is worth noting that most EOCR relays can operate on AC/DC voltages. This is not available in the TeSys T range. The product is to be selected to operate either AC or DC (attached LTMR catalog page) As a close match, P/N EOCR3DM2WRDUW can be substituted by P/N LTMR100MFM. Both datasheets attached 
 
2. EOCRSS05N220 is an electronic overload relay. Its protection adjustment range is: 0.5A to 6A. for operating voltage is 220 VAC, then the closest substitute could be P/N LT4706M7A (datasheet attached). 
 
3. EOCRSS30220 is an electronic overload relay. Its protection adjustment range is: 3A to 30A. for operating voltage is 220 VAC, then the closest substitute could be P/N LT4730M7A (datasheet attached) 
 
4. EOCRSS60N220 is an electronic overload relay. Its protection adjustment range is: 5A to 60A. for operating voltage is 220 VAC, then the closest substitute could be P/N LT4760M7A (datasheet attached) 
Was this helpful?
What can we do to improve the information ?