While communicating P132 by using Micom S1 Studio V.5.3.0, I have faced some error message during transferring setting files. Only few configured data are only transferred to P132 relay.

For Example, In Parameters – Configured Parameters – Outputs, Inputs, LEDS, etc are transferred successfully. 
But in Operation – Control & Testing – Output the address no 003.042 which I have assigned for Tripping function is not transferred to the P132 relay. 
 

Resolution for this kind of issue 

Sometime this kind of error occur when you upload a setting file to the P30 series .In this case you must send the parameters to  the relay one by one. 

Open the setting file and  right click on the parameter not sent then click "send data to the device" ,Normally it will work fine

Please check the attached file to check the procedure .

 