Please advice if we can use tesys T for normal outgoing power feeders ?

Kindly be informed that there is no official recommendation for using the Tesys T for Feeder control as the relay is dedicated for Motor control. 

It you request to use it for feeder control , but we cannot modify or remove the protections functions and captions related to Motor control e.g. Jam , Long Start , Motor Rating , Motor type etc. neither in the Configuation media ( software/operator panel) or in the documentation. 

We generally recommend the Sepam / Micom relays for Feeder protection and Automation.