I got Major fault error as shown in the attached picture (Diagnosis page in SFT software) I Would like to have your support to solve this error ?

After you face this error you need to generate SAV report 

After Generating SAV report using SFT SAV tool. as The SAV report will give us the needed information about the Sepam and which specific fault it received. 

You can download SFT SAV tool at this Box link à

In case you found the error in the SAV report as 

The Case resolution will be 

15 CCx can be related to absence of current measuring input socket or sensor interface current missing CCA630, CCA634 or CCA670. This can be corrected by adding the missing parts