What are the indicators and how can I look for forced objects on TSX Micro and TSX Premium?

 System word %SW108 contains the number of forced bits. This information is also available in the processor adjustment window. Bits are forced from an animation table. System word %SW109 contains the number of forced analog channels. A channel is written to a forced value during adjustment by right-clicking on the channels then on "Properties". There is however no automatic search method.