Product FAQs

Ask a Question

Can ATV312H***N4410 support pulse input reference? How can we set up the drive to accept pulse input as speed reference?
The specific version of drive having part reference like ATV312H***N4410 is designed  to support speed control with a pulse input reference of 24V...
How to configure audible alarms as per different alarm priorities in Vijeo Citect?
Follow below mentioned steps to configure different audible alarms as per alarm priorities. 1. In Citect Project editor open Computer setup editor...
I have installed Somove lite version 2.4 but not able to connect or create program of Tesys T or any of drive. How to solve the problem?
The DTM files for all Drives, Tesys T, Tesys U were part of Somove Lite software download until Somove Version 1.9.2.0. But the Somove version 2.0...
What are the System requirements for Unity Pro V11.1?
Attached document describes the validated platforms for windows operating system.
Does Unity Pro 4.1 support Windows 7 64 bit ?
Unity pro is qualified to work on below system requirements.  Windows 7 platform is no more validated for unity pro 4.1. System with Microsoft Windows...
What are the safety clearance dimensions for a LC1B range contactor switching with the DC voltage.
The safety clearance distances are as per the attached table. These values are given for AC voltage; however these values are same as in case of DC...
Can the TeSys range overload relays be used in DC application?
The overload relay with the bimetal technology (Thermal Overload) only can be used in DC application.  Tesys LRD Range Tesys LRD thermal overload...
What is the error meaning "No reply from PLC within Timeout period" in Vijeo Designer HMI ?
This happens if a valid reply has not been received from the PLC within the specified timeout period and the communication packet was retried the...
What are the various parts included in the LAD91217 Star Delta connection kit.
The different parts contained in the LAD91217 Star Delta connection kit is as shown in the below figure.
How to use Write_Var block with BMXNOC0401 communication module?
See below an example of Write_Var block for writing Modbus slave data through ETG100 gateway.​ In ADDM block '0.3.0{192.168.1.21}1.TCP.MBS' where...
Results 1 - 10 of 100