TECHNICAL INFORMATION
Dimensions (W x H x D)
600 x 2400 x 670
600 x 2400 x 800
800 x 2400 x 670
800 x 2400 x 800
400 x 2400 x 670 Term. Cubicle
400 x 2400 x 800 Term. Cubicle
Rated Insulation Voltage
1000 Volt AC at 50Hz
Main busbars
Number of conductors
Rated currents
Short-time withstand
4 conductors - L1, L2, L32, Earth
5 conductors - L1, L2, L3, N, Earth
Up to 6000 Amps
Up to 100kA RMS / 1 Sec, 220kA Peak
Dropper busbars
Rated Currents
Short-time withstand
Up to 1000 Amp
Up to 75kA RMS / 1 Sec, 165kA Peak
Auxilliary busbars
Number of conductors
Up to 4 conductors on each side
Construction
Forms or separation
Form 3b, Form 4a
Protective coating
Metal treatment
Powder coating
De-rust, De-grease, Iron Phosphate and passivate
Epoxy polyester (Interior)
Polyurethane (Exterior)
FEATURES
Segregated, Modular construction
Top or bottom Main busbars
Top or bottom Cable Entry
Seperate termination cubicle adjacent to starter panel