Does Easypact MVS comply with total safety that shall be guaranteed without the need of phases barriers till 1150V AC.

The Interphase barrier are used If the insulation distance between phases is not sufficient (< 14 mm), (taking into account the safety clearances). 
N.B.The Rated insulation voltage is 1000V and the Rated operational voltage (V AC 50/60 Hz) 690V AC.