For Accusine SWP,what does mean the alarm message "Internal overtemp" and what action to be taken?


This alarm message means that The AccuSine SWP has been stopped by the thermal protection thus avoiding damage to the equipment.
Corrective Actions:
Check that the 3 ventilators are operating correctly,that the air vents are clean and check the temperature of the room.
The temperature tolerances permitted are defined in the AccuSine SWP Installation Manual 990–4530.