The power factor is displayed incorrectly on the Varplus logic controller. What action to be taken?

The cause may be that:
  • The connection detection was not performed
  • The phase angle was adjusted manually false
  • Offset reactive power is adjusted
The action to be taken:
  • Start "AI" in "SETUP" menu
  • Check point 206 in the "EXPERTMENU" and correct the phase angle if necessary
  • With the compensation system, a transformer is compensated. The displayed Pf is in front of the transformer. The displayed Pf is in front of the transformer