Is it possible to communicate with Varplus logic relay in Modbus?

The Varlogic VL 6/12 offer in standard a modus RS485 communication port.
The RS485 line Speed can be set from 1200 bds up to 115600 bds, with parity None, Event or Odd.
Slave number can be set from 1 to 247.
4 wires screw Terminal: 0V / shield / D0- / D1+.
For modbus table and details about connection ,please refer to the attached  Varplus logic VL Modbus manual.